The EAHC21 is an automatic control system for up to two heat recovery units (standard). It is designed to be used in conjunction with exodraft chimney fans and heat exchangers. The heart of the EAHC21 system is a WAGO PLC control with various digital and analogue I/O modules connected to terminal blocks for easy interface. A 7” touch screen allows for monitoring and configuration of the system.
The EAHC21 control monitors and maintains specific pressures and temperatures by controlling the speed of a chimney fan and by regulating the water temperature in the hydraulic system. It also monitors the pressure loss in the heat exchanger as well as other critical values in the heat exchanger system. The different pressures in the system are measured by XTP 150 sensors and the temperatures by PT1000 sensors. If the pressure and temperature setpoints of the system reach critical levels, a warning will be shown on the display and an alarm relay will be activated.
The touch-enabled display gives the user the option to monitor the values of both the flue and hydraulic systems. The latest warnings and trend curves are visible for both systems. With a ow meter installed, the user can continuously monitor the production (kW) of the system.
Advanced heat recovery control
The touch-enabled display gives the user the option to monitor the values of both the flue and hydraulic systems. The latest warnings and trend curves are visible for both systems. With a flow meter installed, the user can continuously monitor the production (kW) of the system.
Features & Benefits
- Input and output to 2 heat recovery units and 2 buffer tanks
- Remote access via web server
- Easy installation
- Expandable I/O capacity
- Multiple bus compatible (BACnet, MODBUS/IP, KNX, PROFIBUS)
- Integrated touch display with user-friendly interface
- 3 standard motor configuration options
Technical Specifications
Description | EACH21 TRIAC 3201067 | EACH21 VFD+TRIAC 3201071 | EACH21 VFD 3201068 |
---|---|---|---|
Height x width x depth | 700 x 500 x 250 mm | 700 x 500 x 250 mm | 700 x 500 x 250 mm |
Weight | 30 kg | 30 kg | 30 kg |
Density Class/ material | IP54 / Steel | IP54 / Steel | IP54 / Steel |
Voltage | 1×230 V AC +10%, 50 Hz | 1×230 V AC +10%, 50 Hz | 3×400 V AC +10%, 50 Hz |
Rated Current | 4A | 20A | 25A |
Temperature | 0 to 55°C | 0 to 55°C | 0 to 55°C |
HMI | 7″ Resistive Touch LCD 800×480 | 7″ Resistive Touch LCD 800×480 | 7″ Resistive Touch LCD 800×480 |
Inputs: | |
---|---|
Digital potential-free | 2 |
Digital 24-230 V AC/DC | 2 |
XTP-sensor 0-10V Analog | 4 |
Flowsensor 0-20 mA / 0.3-15 m3/h | 2 |
PT100/PT1000 Temperatursensor | 8 |
Outputs: | |||
---|---|---|---|
Digital potential-free | 6 – 250V/8A | 6 – 250V/8A | 6 – 250V/8A |
Digital 230V output | 4 – 230V/6A total | 4 – 230V/6A total | 4 – 230V/6A total |
For general purposes potential-free | 2 – 250V/8A | 2 – 250V/8A | 2 – 250V/8A |
0-10V Analog | 4 | 4 | 4 |
Chimney fan output | 2 x 70-230V / 4A | 2 x 70-230V / 4A + 1 x 3x230V / 1.5kW | 2 x 3x400V / 1.5kW |
Tryksensor data: | |
---|---|
Dimensions (w x h x d) | 75 x 92 x 49 mm |
Operating Temperature | 0 to 70 °C |
Monitoring Interval | 0 to +150 Pa (0 to 250 Pa) |
Max. distance between control unit and XTP sensor | 100 m |
I-rating | IP54 |
mA | 30 |
Communication Possibilities | BACnet, MODBUS/IP, KNX, MODBUS, PROFIBUS |