The EAHC21 is an automatic control system for up to two heat recovery units (standard). It is designed to be used in conjunction with exodraft chimney fans and heat exchangers. The heart of the EAHC21 system is a WAGO PLC control with various digital and analogue I/O modules connected to terminal blocks for easy interface. A 7” touch screen allows for monitoring and configuration of the system.

The EAHC21 control monitors and maintains specific pressures and temperatures by controlling the speed of a chimney fan and by regulating the water temperature in the hydraulic system. It also monitors the pressure loss in the heat exchanger as well as other critical values in the heat exchanger system. The different pressures in the system are measured by XTP 150 sensors and the temperatures by PT1000 sensors. If the pressure and temperature setpoints of the system reach critical levels, a warning will be shown on the display and an alarm relay will be activated.

The touch-enabled display gives the user the option to monitor the values of both the flue and hydraulic systems. The latest warnings and trend curves are visible for both systems. With a ow meter installed, the user can continuously monitor the production (kW) of the system.

Download Appraisal FormDownload Brochure

Advanced heat recovery control

The touch-enabled display gives the user the option to monitor the values of both the flue and hydraulic systems. The latest warnings and trend curves are visible for both systems. With a flow meter installed, the user can continuously monitor the production (kW) of the system.

Features & Benefits

  • Input and output to 2 heat recovery units and 2 buffer tanks
  • Remote access via web server
  • Easy installation
  • Expandable I/O capacity
  • Multiple bus compatible (BACnet, MODBUS/IP, KNX, PROFIBUS)
  • Integrated touch display with user-friendly interface
  • 3 standard motor configuration options

Technical Specifications

DescriptionEACH21 TRIAC
3201067
EACH21 VFD+TRIAC
3201071
EACH21 VFD
3201068
Height x width x depth700 x 500 x 250 mm700 x 500 x 250 mm700 x 500 x 250 mm
Weight30 kg30 kg30 kg
Density Class/ materialIP54 / SteelIP54 / SteelIP54 / Steel
Voltage1×230 V AC +10%, 50 Hz1×230 V AC +10%, 50 Hz3×400 V AC +10%, 50 Hz
Rated Current4A20A25A
Temperature0 to 55°C0 to 55°C0 to 55°C
HMI7″ Resistive Touch LCD 800×4807″ Resistive Touch LCD 800×4807″ Resistive Touch LCD 800×480
Inputs:
Digital potential-free2
Digital 24-230 V AC/DC2
XTP-sensor 0-10V Analog4
Flowsensor 0-20 mA / 0.3-15 m3/h2
PT100/PT1000 Temperatursensor8
Outputs:
Digital potential-free6 – 250V/8A6 – 250V/8A6 – 250V/8A
Digital 230V output4 – 230V/6A total4 – 230V/6A total4 – 230V/6A total
For general purposes potential-free2 – 250V/8A2 – 250V/8A2 – 250V/8A
0-10V Analog444
Chimney fan output2 x 70-230V / 4A2 x 70-230V / 4A + 1 x
3x230V / 1.5kW
2 x 3x400V / 1.5kW
Tryksensor data:
Dimensions (w x h x d)75 x 92 x 49 mm
Operating Temperature0 to 70 °C
Monitoring Interval0 to +150 Pa (0 to 250 Pa)
Max. distance between control unit and XTP sensor100 m
I-ratingIP54
mA30
Communication PossibilitiesBACnet, MODBUS/IP, KNX, MODBUS, PROFIBUS

Need Help?

Chat with our support team today to find the right boiler for your project or to book a service.

Click Here